Echomax® XRS-5 ultrasonic transducer provides reliable, continuous level monitoring of liquids and slurries in narrow lift stations/ wet wells, flumes,
weirs and filter beds using a beam angle of just 10° and a CSM rubber face. The XRS-5 is non-contacting with a measuring range from 0.3 to 8 m (1 to 26 ft).
Advanced echo processing ensures reliable data even in conditions with obstructions, turbulence and foam. The hermetically sealed
CSM rubber face and the PVDF copolymer enclosure are designed for maximum resistance to methane, salt water,
caustics and harsh chemicals common to wastewater installations. With an IP68 degree of protection,
this rugged sensor is fully submersible in the event of flood conditions. Use a submergence shield if full submergence is possible in the application.
A submergence shield will maintain a high level reading output during submerged conditions.
The low-cost XRS-5 transducer is compatible with a full range of Siemens controllers, from a basic system for high/low alarm
or simple pump control, up to advanced control systems with communications, telemetry and SCADA integration capabilities.
Overview
EchoMax XRS-5 ultrasonic transducer provides reliable, continuous level monitoring of liquids and slurries in narrow lift stations/wet wells,
flumes, weirs and filter beds using a beam angle of just 10° and a CSM rubber face.
Benefits
Narrow beam angle of only 10°
Chemically resistant PVDF copolymer enclosure and CSM rubber face
Measuring range: 8 m (26 ft) for measurement of liquids and slurries
Fully submersible: IP68 degree of protection
Easy installation with 1" NPT or R 1" BSPT connection
Application
The XRS-5 is non-contacting with a measuring range from 0.3 to 8 m (1 to 26 ft). Advanced echo processing
ensures reliable data even in conditions with obstructions, turbulence, and foam.
The hermetically sealed CSM rubber face and the PVDF copolymer enclosure are designed for maximum resistance
to methane, salt water, caustics, and harsh chemicals common to wastewater installations. With an IP68 degree of
protection, this rugged sensor is fully submersible in the event of flood conditions. Use a submergence shield if full
submergence is possible in the application. A submergence shield will maintain a high level reading output during submerged conditions.
The low-cost XRS-5 transducer is compatible with a full range of Siemens controllers, from a basic system for high/low alarm or simple pump control,
up to advanced control systems with communications, telemetry and SCADA integration capabilities.
Key Applications: wet wells, flumes, weirs, filter beds
Technical specifications
Mode of operation | |
Measuring principle | Ultrasonic transducer |
Input | |
Measuring range | 0.3 ... 8 m (1 ... 26 ft), dependent on application |
Output | |
Frequency | 44 kHz |
Beam angle | 10° |
Accuracy | |
Temperature error | Compensated by integral temperature sensor |
Rated operating conditions | |
Vessel pressure | Normal atmospheric pressure |
Ambient Conditions | |
| -20 ... +65 °C (-4 ... +149 ° F) |
Design | |
Weight (approximate shipping weight of sensor with standard cable length) | 1.2 kg (2.6 lb) |
Material (enclosure) | PVDF copolymer enclosure and CSM face |
Process connection | 1" NPT [(Taper), ANSI/ASME B1.20.1] or R 1" [(BSPT), EN 10226] |
Degree of protection | IP65/IP68 |
Cable connection | 2-core shielded/twisted, 0.5 mm2 (20 AWG), PVC sheath |
Cable (max. length) |
|
Options | |
Flange version | Factory flange with PTFE face for ASME, EN or JIS configuration |
Submergence shield | For applications with flooding possible |
Certificates and approvals | CE, RCM, KCC CSA Class I, Div. 2, Groups A, B, C, D, Class II, Div. 1 Groups E, F, G FM Class I, Zone 1, AEx m IIC, T6 Class II, III, Div. 1, Groups E, F, G T6 ATEX II 2GD / IECEx / INMETRO Ex mb IIC T6 Gb, Ex tb IIIC T85 °C Db |