SIEMENS Hot Sale SITRANS LC300 Capacitance level measurement Process Instrumentation Level Measurement New & Original with good Price
- Product description
- Contact us
SIEMENS SITRANS LC300 Capacitance level measurement
Process Instrumentation Level Measurement New & Original
SITRANS LC300 is an inverse frequency shift capacitance continuous level transmitter for liquids and solids applications.
It is ideal for standard industrial applications in chemical, hydrocarbon processing, food and beverage and mining, aggregate and cement industries.
SITRANS LC300 is a 2-wire level measurement instrument combining a sophisticated, yet easy-to-adjust microprocessor with field-proven probes.
It is available in two versions: rod and cable. SITRANS LC300 has a stainless steel process connection with PFA-lined probe.
Materials with low or high dielectric properties are accurately measured and Active-Shield technology helps in ignoring the effects of buildup near vessel nozzle.
Overview
SITRANS LC300 is an inverse frequency shift capacitance continuous level transmitter for liquid, interface, and solid applications.
It is ideal for standard industrial applications in chemical, hydrocarbon processing, food and beverage, water, wastewater, mining, aggregate, and cement industries.
Benefits
Active-Shield technology so measurement is unaffected by material buildup in active shield section
Highly accurate and reliable PFA-lined probes
Integrated local LCD display
2-wire (4 to 20 mA) current loop design
Current signaling according to NAMUR NE 43
Push-button calibration and programming
Stilling well (ground tube) version for low dielectric media, agitated materials, and non-metallic vessels
Application
SITRANS LC300 is a 2-wire level measurement instrument combining a sophisticated, yet easy-to-adjust microprocessor with field-proven probes.
It is available in four versions: rod, rod with stilling well, cable with PFA insulation, and cable without PFA insulation.
Materials with low or high dielectric properties are accurately measured and Active-Shield technology
helps in ignoring the effects of buildup or condensation near vessel nozzle.
Key Applications: conductive (dK ≥ 20) and non-conductive (dK < 20) media including: liquids and solids in standard industrial processes,
bulk solids applications involving dust, and chemical processes involving vapor
Probe Applications | |
---|---|
Rod version | Conductive liquids, slurries or solids |
Rod version with stilling well |
|
Cable version | Non-conductive solids or liquids |
PFA coated cable version | Conductive or sticky liquids, slurries or solids |
Technical specifications
Input | |
Measuring range | 1.66 ... 3 300 pF |
Span | Min. 3.3 pF |
Output | |
Loop current | Continuous signal 4 ... 20 mA/20 ... 4 mA according to NAMUR 43 |
Accuracy (transmitter) | |
Temperature stability | 0.25 % of actual capacitance value |
Non-linearity and repeatability | < 0.4 % of full scale and actual measurement value |
Accuracy | Deviation < 0.5 % of actual measurement value |
Rated operating conditions1) | |
Ambient conditions | |
| -40 ... +85 °C (-40 ... +185 °F)2)3) |
| I |
| 4 |
| Type 4/NEMA 4/IP65 (optional IP68) |
Installation conditions | |
| Indoor/outdoor |
| -1 ... +35 bar g (-14.6 ... +511 psi g) |
| -40 ... +200 ºC (-40 ... +392 ºF)4) |
| 1.5 |
| 5 |