Phoenix Surge protection device - DT-LAN-CAT.6+ - 2881007
Surge protection in accordance with Class EA (CAT6A), for Gigabit Ethernet (up to 10 Gbps), token ring, FDDI/CDDI, ISDN, and DS1.
Suitable for Power over Ethernet (PoE+) “Mode A” and “Mode B”. RJ45 attachment plug with separate grounding cable and ground connection snap-on foot for NS 35 DIN rails.
Key Commercial Data
Orderkey | 2881007 |
---|
Packing unit | 1 pc |
---|
Catalog page | Page 142 (C-4-2017) |
---|
GTIN | 4046356151900 |
---|
Weight per Piece (excluding packing) | 320.000 g |
---|
Custom tariff number | 85363010 |
---|
Country of origin | DE (Germany) |
---|
Dimensions
Height | 102 mm |
---|
Width | 25 mm |
---|
Depth | 63.5 mm |
---|
Ambient conditions
Ambient temperature (operation) | -40 °C ... 70 °C |
---|
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
---|
Degree of protection | IP20 |
---|
General
Housing material | Zinc die-cast |
---|
Color | silver/black |
---|
Mounting type | Connection-specific attachment plug and DIN rail, 35 mm |
---|
Type | Attachment plug for DIN rail mounting |
---|
Number of positions | 8 |
---|
Direction of action | Line-Line & Line-Ground/Shield |
---|
Protective circuit
IEC test classification | B2 |
---|
| C1 |
---|
| C2 |
---|
| C3 |
---|
| D1 |
---|
Maximum continuous voltage UC (wire-wire) | ≤ 3.3 V DC (± 60 V DC/PoE+) |
---|
Rated current | ≤ 1.5 A (25 °C) |
---|
Operating effective current IC at UC | ≤ 1 µA |
---|
Residual current IPE | ≤ 400 µA |
---|
Nominal discharge current In (8/20) µs (line-line) | 100 A |
---|
Nominal discharge current In (8/20) µs (line-earth) | 2 kA (per signal pair) |
---|
Total discharge current Itotal (8/20) µs | 10 kA |
---|
Nominal pulse current Ian (10/700) µs (line-line) | ≤ 40 A |
---|
Nominal pulse current Ian (10/700) µs (line-earth) | ≤ 160 A |
---|
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 85 V (PoE) |
---|
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V |
---|
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 9 V |
---|
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V |
---|
Residual voltage at In (line-line) | ≤ 15 V |
---|
| ≤ 100 V (PoE) |
---|
Voltage protection level Up (line-line) | ≤ 9 V (B2 - 1 kV / 25 A) |
---|
| ≤ 100 V (B2 - 1 kV / 25 A - PoE) |
---|
| ≤ 12 V (C3 - 20 A) |
---|
Voltage protection level Up (line-earth) | ≤ 900 V (B2 - 4 kV / 100 A) |
---|
| ≤ 700 V (C2 - 4 kV / 2 kA) |
---|
| ≤ 1 kV (C3 - 80 A) |
---|
Response time tA (line-line) | ≤ 1 ns |
---|
Response time tA (line-earth) | ≤ 100 ns |
---|
Input attenuation aE, sym. | ≤ 1 dB (up to100 MHz/direct measuring) |
---|
| ≤ 1 dB (up to 250 MHz/direct measuring) |
---|
| ≤ 3 dB (up to 500 MHz/direct measuring) |
---|
Near-end crosstalk attenuation | ≥ 35 dB (250 MHz/100 Ω/link) |
---|
| ≥ 45 dB (100 MHz / 100 Ω / Link) |
---|
| ≥ 27 dB (500 MHz / 100 Ω / Link) |
---|
| ≥ 39 dB (250 MHz/100 Ω/direct measuring) |
---|
Capacity (line-line) | typ. 12 pF (f= 1 MHz / VR= 0 V) |
---|
Capacity (line-earth) | typ. 2 pF (f= 1 MHz / VR= 0 V) |
---|
Surge protection fault message | none |
---|
Impulse durability (line-line) | B2 - 1 kV / 25 A |
---|
| C3 - 20 A |
---|
Impulse durability (line-earth) | B2 - 4 kV / 100 A |
---|
| C2 - 4 kV / 2 kA |
---|
| C3 - 80 A |
---|
| D1 - 1 kA |
---|
Connection data
Connection, equipotential bonding
Connection method | DIN rail NS35 |
---|
Standards and Regulations
Standards/specifications | IEC 61643-21 2002 |
---|
| EN 50173-1 2002 |
---|
| ISO/IEC 11801-Am.1 2006 |
---|