Products

Phoenix Surge protection plug - PT 3-HF-12DC-ST - 2858043 New & Original with very competitive price and One year Warranty

New & Original
plug - PT 3-HF-12DC-ST - 2858043
Phoenix Surge protection plug - PT 3-HF-12DC-ST - 2858043 New & Original with very competitive price and One year Warranty
Please contact us for more information.

Phoenix Surge protection plug - PT 3-HF-12DC-ST - 2858043





Surge protection plug for the base element, normal mode voltage coarse and fine protection for two floating signal wires and ground in IT, 

common mode voltage coarse protection to ground/earth. Design: 12 V DC


Key Commercial Data

Orderkey2858043
Packing unit1 pc
Catalog pagePage 169 (C-4-2019)
GTIN4017918878047
Weight per Piece (excluding packing)20.730 g
Custom tariff number85363090
Country of originDE (Germany)


Dimensions

Height45 mm
Width17.7 mm
Depth52 mm
Horizontal pitch1 Div.
Complete module height90 mm
Complete module width17.7 mm
Complete module depth65.5 mm


Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Altitudemax. 2000 m
Degree of protectionIP20


General

Housing materialPA
Flammability rating according to UL 94V-0
Colorblack
Standards for cearances and creepage distancesDIN EN 61664-1

IEC 60664-1
Mounting typeon base element
TypeMale
Number of positions3
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10


Protective circuit

IEC test classificationC1

C2

C3

D1
VDE requirement classC1

C2

C3

D1
Nominal voltage UN12 V DC
Maximum continuous voltage UC14 V DC

9.8 V AC
Rated current450 mA (45 °C)
Operating effective current IC at UC≤ 5 µA
Residual current IPE< 5 µA (with PT 1X2-BE)

< 1 µA (with PT 1X2+F-BE)
Nominal discharge current In (8/20) µs (line-line)10 kA
Nominal discharge current In (8/20) µs (line-earth)10 kA
Nominal discharge current In (8/20) µs (line-signal ground)10 kA
Pulse discharge current Iimp (10/350) µs2.5 kA
Total discharge current Itotal (8/20) µs20 kA
Max. discharge current Imax (8/20) µs maximum (line-line)10 kA
Max. discharge current Imax (8/20) µs maximum (line-earth)10 kA
Nominal pulse current Ian (10/1000) µs (line-line)67 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 55 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 55 V (with PT 1X2-BE)

≤ 700 V (with PT 1X2+F-BE)
Output voltage limitation at 1 kV/µs (line-line) static≤ 25 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 25 V

≤ 40 V (with PT 1X2+F-BE)
Residual voltage at In (line-line)≤ 25 V
Residual voltage at In (line-earth)≤ 40 V (with PT 1X2-BE)
Residual voltage at In (line-signalground)≤ 25 V (with PT 1X2-BE)
Residual voltage with Ian (10/1000) µs (line-line)≤ 25 V
Residual voltage with Ian (10/1000) µs (line-signalground)≤ 25 V
Voltage protection level Up (line-line)≤ 50 V (C3 - 25 A)

≤ 80 V (C1 - 1 kV/500 A)

≤ 110 V (C2 - 10 kV / 5 kA)

≤ 80 V (6 kV / 3 kA)
Voltage protection level Up (line-earth)≤ 50 V (C3 - 25 A)

≤ 85 V (C1 - 1 kV/500 A)

≤ 140 V (C2 - 10 kV / 5 kA)

≤ 100 V (6 kV / 3 kA)
Voltage protection level Up (line-signalground)≤ 50 V (C3 - 25 A)
Response time tA (line-line)≤ 500 ns
Response time tA (line-earth)≤ 500 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 5 MHz / 100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm systemtyp. 60 MHz
Capacity (line-line)typ. 30 pF
Resistance per path2.2 Ω ±10 % (7-8/11-12)
Max. required back-up fuse500 mA (T)
Impulse durability (line-line)C2 - 10 kV / 5 kA

C3 - 67 A
Impulse durability (line-earth)C2 - 10 kV / 5 kA

C3 - 67 A

D1 - 2.5 kA


Connection data

Connection methodScrew connection (in connection with the base element)
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12


Connection, equipotential bonding

Stripping length8 mm
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12


Standards and Regulations

Standards/specificationsEN 61643-21/A1 2009

IEC 61643-21/A1 2008



2858043

Copyright © 2019 Sunup (Wuhan) Industrial Equipment Co., Ltd. All Right Reserved.


Sunup (Wuhan) Industrial Equipment Co., Ltd is not an authorized reseller, agent or affiliate of any brand or manufacturer. All trademarks, brand names and logos whose products are sold on the website are used for identification purposes only and are registered trademarks of their respective owners, all rights reserved. The use of a trademark, brand name or product on our website does not imply that the company trademark or brand belongs to or endorses our website. All products are 100% original, genuine and legally purchased from authorized sources.