Phoenix Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
MCR 3-way signal conditioner, for electrical isolation of analog signals, with spring-cage connection, input signal: 0...20 mA /
4...20 mA, output signal: 0...20 mA / 4...20 mA. Replacement part: 2901999 MINI MCR-2-I-I-PT.
Key Commercial Data
Orderkey | 2864723 |
---|
Packing unit | 1 pc |
---|
Catalog page | Page 97 (C-7-2015) |
---|
GTIN | 4017918974923 |
---|
Weight per Piece (excluding packing) | 63.800 g |
---|
Custom tariff number | 85437090 |
---|
Country of origin | DE (Germany) |
---|
Dimensions
Width | 6.2 mm |
---|
Height | 93.1 mm |
---|
Depth | 102.5 mm |
---|
Ambient conditions
Ambient temperature (operation) | -20 °C ... 65 °C |
---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
---|
Degree of protection | IP20 |
---|
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
---|
Input data
Number of inputs | 1 |
---|
Configurable/programmable | no |
---|
Current input signal | 0 mA ... 20 mA |
---|
| 4 mA ... 20 mA |
---|
Max. input current | 50 mA |
---|
Input resistance current input | approx. 50 Ω |
---|
Output data
Number of outputs | 1 |
---|
Configurable/programmable | no |
---|
Current output signal | 0 mA ... 20 mA |
---|
| 4 mA ... 20 mA |
---|
Max. output current | 28 mA |
---|
Load/output load current output | < 500 Ω (at 20 mA) |
---|
Ripple | < 20 mVPP (at 500 Ω) |
---|
Power supply
Nominal supply voltage | 24 V DC |
---|
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
---|
Max. current consumption | < 20 mA |
---|
Power consumption | < 450 mW |
---|
Connection data
Connection method | Spring-cage connection |
---|
Stripping length | 8 mm |
---|
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
---|
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
---|
Conductor cross section AWG | 24 ... 12 |
---|
General
No. of channels | 1 |
---|
Maximum transmission error | ≤ 0.1 % (of final value) |
---|
Maximum temperature coefficient | < 0.01 %/K |
---|
Temperature coefficient, typical | < 0.002 %/K |
---|
Limit frequency (3 dB) | approx. 100 Hz |
---|
Step response (10-90%) | approx. 3.2 ms |
---|
Protective circuit | Transient protection |
---|
Electrical isolation | Basic insulation according to EN 61010 |
---|
Overvoltage category | II |
---|
Degree of pollution | 2 |
---|
Rated insulation voltage | 50 V AC/DC |
---|
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
---|
Electromagnetic compatibility | Conformance with EMC directive |
---|
Noise emission | EN 61000-6-4 |
---|
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
---|
Color | green |
---|
Housing material | PBT |
---|
Mounting position | any |
---|
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
---|
Conformance | CE-compliant |
---|
ATEX | II 3 G Ex nA IIC T4 Gc X |
---|
UL, USA/Canada | UL 508 Recognized |
---|
| Class I, Div. 2, Groups A, B, C, D T5 |
---|
GL | GL EMC 2 D |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
---|
EMC data
Designation | Electromagnetic RF field |
---|
Standards/regulations | EN 61000-4-3 |
---|
Typical deviation from the measuring range final value | 10 % |
---|
Designation | Fast transients (burst) |
---|
Standards/regulations | EN 61000-4-4 |
---|
Typical deviation from the measuring range final value | 10 % |
---|
Designation | Conducted interferences |
---|
Standards/regulations | EN 61000-4-6 |
---|
Typical deviation from the measuring range final value | 10 % |
---|
Standards and Regulations
Electromagnetic compatibility | Conformance with EMC directive |
---|
Noise emission | EN 61000-6-4 |
---|
Connection in acc. with standard | CUL |
---|
Designation | Electromagnetic RF field |
---|
Standards/regulations | EN 61000-4-3 |
---|
| EN 61000-4-4 |
---|
Designation | Conducted interferences |
---|
Standards/regulations | EN 61000-4-6 |
---|
Electrical isolation | Basic insulation according to EN 61010 |
---|
Conformance | CE-compliant |
---|
ATEX | II 3 G Ex nA IIC T4 Gc X |
---|
UL, USA/Canada | UL 508 Recognized |
---|
| Class I, Div. 2, Groups A, B, C, D T5 |
---|
GL | GL EMC 2 D |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
---|