Phoenix Signal conditioner - MINI MCR-SL-I-I - 2864406
MCR 3-way isolating amplifier, for electrical isolation of analog signals, with screw connection,
input signal: 0(4) mA ... 20 mA, output signal: 0(4) mA ... 20 mA
Product Description
The 6.2 mm wide standard signal 3-way isolating amplifier MINI MCR-SL-I-I(-SP) is used for electrical isolation,
amplification and filtering of standard signals.
On the input and output side, the analog standard signals 0...20 mA or 4...20 mA are available, electrically isolated.
Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in
conjunction with the DIN rail connector.
Key Commercial Data
Orderkey | 2864406 |
---|
Packing unit | 1 pc |
---|
Catalog page | Page 97 (C-7-2015) |
---|
GTIN | 4017918956158 |
---|
Weight per Piece (excluding packing) | 85.000 g |
---|
Custom tariff number | 85437090 |
---|
Country of origin | DE (Germany) |
---|
Dimensions
Width | 6.2 mm |
---|
Height | 93.1 mm |
---|
Depth | 102.5 mm |
---|
Ambient conditions
Ambient temperature (operation) | -20 °C ... 65 °C |
---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
---|
Degree of protection | IP20 |
---|
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
---|
Input data
Number of inputs | 1 |
---|
Configurable/programmable | no |
---|
Current input signal | 0 mA ... 20 mA |
---|
| 4 mA ... 20 mA |
---|
Max. input current | 50 mA |
---|
Input resistance current input | approx. 50 Ω |
---|
Output data
Number of outputs | 1 |
---|
Configurable/programmable | no |
---|
Current output signal | 0 mA ... 20 mA |
---|
| 4 mA ... 20 mA |
---|
Max. output current | 28 mA |
---|
Load/output load current output | < 500 Ω (at 20 mA) |
---|
Ripple | < 20 mVPP (at 500 Ω) |
---|
Power supply
Nominal supply voltage | 24 V DC |
---|
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
---|
Max. current consumption | < 20 mA |
---|
Power consumption | < 450 mW |
---|
Connection data
Connection method | Screw connection |
---|
Stripping length | 12 mm |
---|
Screw thread | M3 |
---|
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
---|
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
---|
Conductor cross section AWG | 26 ... 12 |
---|
General
No. of channels | 1 |
---|
Maximum transmission error | ≤ 0.1 % (of final value) |
---|
Maximum temperature coefficient | < 0.01 %/K |
---|
Temperature coefficient, typical | < 0.002 %/K |
---|
Limit frequency (3 dB) | approx. 100 Hz |
---|
Step response (10-90%) | approx. 3.2 ms |
---|
Protective circuit | Transient protection |
---|
Electrical isolation | Basic insulation according to EN 61010 |
---|
Overvoltage category | II |
---|
Degree of pollution | 2 |
---|
Rated insulation voltage | 50 V AC/DC |
---|
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
---|
Electromagnetic compatibility | Conformance with EMC directive |
---|
Noise emission | EN 61000-6-4 |
---|
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
---|
Color | green |
---|
Housing material | PBT |
---|
Mounting position | any |
---|
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
---|
Conformance | CE-compliant |
---|
ATEX | II 3 G Ex nA IIC T4 Gc X |
---|
UL, USA/Canada | UL 508 Recognized |
---|
| Class I, Div. 2, Groups A, B, C, D T5 |
---|
GL | GL EMC 2 D |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
---|
EMC data
Designation | Electromagnetic RF field |
---|
Standards/regulations | EN 61000-4-3 |
---|
Typical deviation from the measuring range final value | 10 % |
---|
Designation | Fast transients (burst) |
---|
Standards/regulations | EN 61000-4-4 |
---|
Typical deviation from the measuring range final value | 10 % |
---|
Designation | Conducted interferences |
---|
Standards/regulations | EN 61000-4-6 |
---|
Typical deviation from the measuring range final value | 10 % |
---|
Standards and Regulations
Electromagnetic compatibility | Conformance with EMC directive |
---|
Noise emission | EN 61000-6-4 |
---|
Connection in acc. with standard | CUL |
---|
Designation | Electromagnetic RF field |
---|
Standards/regulations | EN 61000-4-3 |
---|
| EN 61000-4-4 |
---|
Designation | Conducted interferences |
---|
Standards/regulations | EN 61000-4-6 |
---|
Electrical isolation | Basic insulation according to EN 61010 |
---|
Conformance | CE-compliant |
---|
ATEX | II 3 G Ex nA IIC T4 Gc X |
---|
UL, USA/Canada | UL 508 Recognized |
---|
| Class I, Div. 2, Groups A, B, C, D T5 |
---|
GL | GL EMC 2 D |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
---|
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
---|