Products

Phoenix Signal duplicator - MINI MCR-SL-UI-2I-SP - 2864804 New & Original with very competitive price and One year Warranty

New & Original
MCR-SL-UI-2I-SP - 2864804
Phoenix Signal duplicator - MINI MCR-SL-UI-2I-SP - 2864804 New & Original with very competitive price and One year Warranty
Please contact us for more information.

Phoenix Signal duplicator - MINI MCR-SL-UI-2I-SP - 2864804



MCR 4-way signal duplicator for electrical isolation and doubling of analog signals with spring-cage connection, 

order configuration. Replacement part: 2905027 MINI MCR-2-UI-2UI-PT-C.


Product Description

The 6.2 mm wide configurable 4-way isolating amplifier MINI MCR-SL-UI-2I-... is used for electrical isolation, conversion, 

amplification and filtering of standard signals.On the input side, the analog standard signals 0...20 mA, 4...20 mA, 

0...10 V or 1...5V can be selected, on the output side there are two current 

outputs that can be set independently of one another with a 0...20 mA-, or 4...20mA signal, electrically isolated (4-way isolation).

The DIP switches, which can be accessed on the side of the housing, can be used to configure the input and output signal ranges.
Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in 

conjunction with the DIN rail connector.


Key Commercial Data

Orderkey2864804
Packing unit1 pc
Catalog pagePage 98 (C-7-2015)
Weight per Piece (excluding packing)60.000 g
Custom tariff number85437090
Country of originDE (Germany)


Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm


Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Degree of protectionIP20
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.


Input data

Number of inputs1
Configurable/programmableYes, preconfigured
Voltage input signal0 V ... 10 V (please indicate if different setting when ordering)

1 V ... 5 V
Current input signal0 mA ... 20 mA

4 mA ... 20 mA
max. input voltage30 V
Max. input current50 mA
Input resistance of voltage inputapprox. 100 kΩ
Input resistance current inputapprox. 50 Ω


Output data

Number of outputs2
Configurable/programmableYes, preconfigured
Current output signal2x 0 mA ... 20 mA

2x 4 mA ... 20 mA
Max. output currentapprox. 22 mA
Load/output load current output≤ 250 Ω (at 20 mA)
Ripple< 20 mVPP (at 250 Ω)


Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption< 30 mA (at 24 V DC incl. load)
Power consumption< 600 mW


Connection data

Connection methodSpring-cage connection
Stripping length8 mm
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12


General

No. of channels2
Maximum transmission error≤ 0.2 % (of final value)
Transmission error, typical< 0.1 %
Maximum temperature coefficient< 0.01 %/K
Temperature coefficient, typical< 0.004 %/K
Limit frequency (3 dB)approx. 35 Hz
Protective circuitTransient protection
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage50 V AC/DC
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
Assembly instructionsThe T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value5 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value5 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value5 %


Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Connection in acc. with standardCUL
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3

EN 61000-4-4

EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationBasic insulation according to EN 61010
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2


MCR-SL-UI-2I-NC details2


MCR-SL-UI-2I-NC


Copyright © 2019 Sunup (Wuhan) Industrial Equipment Co., Ltd. All Right Reserved.


Sunup (Wuhan) Industrial Equipment Co., Ltd is not an authorized reseller, agent or affiliate of any brand or manufacturer. All trademarks, brand names and logos whose products are sold on the website are used for identification purposes only and are registered trademarks of their respective owners, all rights reserved. The use of a trademark, brand name or product on our website does not imply that the company trademark or brand belongs to or endorses our website. All products are 100% original, genuine and legally purchased from authorized sources.