Phoenix Signal duplicator - MINI MCR-SL-UI-2I-NC - 2864176 New & Original with very competitive price and One year Warranty
- Product description
- Contact us
Phoenix Signal duplicator - MINI MCR-SL-UI-2I-NC - 2864176
4-way signal duplicator for electrical isolation and duplication of analog signals with screw connection, standard configuration
Product Description
The 6.2 mm wide configurable 4-way isolating amplifier MINI MCR-SL-UI-2I-... is used for electrical isolation,
conversion, amplification and filtering of standard signals.
On the input side, the analog standard signals 0...20 mA, 4...20 mA, 0...10 V or 1...5V can be selected,
on the output side there are two current outputs that can be set independently
of one another with a 0...20 mA-, or 4...20mA signal, electrically isolated (4-way isolation).
The DIP switches, which can be accessed on the side of the housing, can be used to configure
the input and output signal ranges. Power (19.2 V DC to 30 V DC) can be supplied through connection
terminal blocks on the modules or in conjunction with the DIN rail connector.
Key Commercial Data
Orderkey | 2864176 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 98 (C-7-2015) |
GTIN | 4017918974800 |
Weight per Piece (excluding packing) | 95.000 g |
Custom tariff number | 85437090 |
Country of origin | DE (Germany) |
Dimensions
Width | 6.2 mm |
---|---|
Height | 93.1 mm |
Depth | 102.5 mm |
Ambient conditions
Ambient temperature (operation) | -20 °C ... 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Degree of protection | IP20 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
Number of inputs | 1 |
---|---|
Configurable/programmable | Yes, unconfigured |
Voltage input signal | 0 V ... 10 V (please indicate if different setting when ordering) |
1 V ... 5 V | |
Current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
max. input voltage | 30 V |
Max. input current | 50 mA |
Input resistance of voltage input | approx. 100 kΩ |
Input resistance current input | approx. 50 Ω |
Output data
Number of outputs | 2 |
---|---|
Configurable/programmable | Yes, unconfigured |
Current output signal | 2x 0 mA ... 20 mA |
2x 4 mA ... 20 mA | |
Max. output current | approx. 22 mA |
Load/output load current output | ≤ 250 Ω (at 20 mA) |
Ripple | < 20 mVPP (at 250 Ω) |
Power supply
Nominal supply voltage | 24 V DC |
---|---|
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Max. current consumption | < 30 mA (at 24 V DC incl. load) |
Power consumption | < 600 mW |
Connection data
Connection method | Screw connection |
---|---|
Stripping length | 12 mm |
Screw thread | M3 |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 12 |
General
No. of channels | 2 |
---|---|
Maximum transmission error | ≤ 0.2 % (of final value) |
Transmission error, typical | < 0.1 % |
Maximum temperature coefficient | < 0.01 %/K |
Temperature coefficient, typical | < 0.004 %/K |
Limit frequency (3 dB) | approx. 35 Hz |
Protective circuit | Transient protection |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 50 V AC/DC |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Housing material | PBT |
Mounting position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T5 | |
GL | GL EMC 2 D |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
EMC data
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 5 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 5 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 5 % |
Standards and Regulations
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
EN 61000-4-5 | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T5 | |
GL | GL EMC 2 D |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |