IFM SI5010 Flow monitor New & Original with very competitive price and One year Warranty

- Product description
- Contact us
IFM SI5010 Flow monitor New & Original with very competitive price and One year Warranty
Reliable monitoring of liquids and gases in pipes
Variable process connection using adapters
Easy setting of the switch points for quick set-up
Robust stainless steel housing for use in harsh industrial environments
LED bar graph for indication of switch point and flow
Product characteristics | |
---|---|
Number of inputs and outputs | Number of digital outputs: 1 |
Process connection | M18 x 1,5 internal thread |
Application | |
Media | Liquids; Gases |
Medium temperature [°C] | -25...80 |
Pressure rating [bar] | 300 |
MAWP (for applications according to CRN) [bar] | 208 |
Liquids | |
Medium temperature [°C] | -25...80 |
Gases | |
Medium temperature [°C] | -25...80 |
Electrical data | |
Operating voltage [V] | 18...36 DC |
Current consumption [mA] | < 60 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 10 |
Inputs / outputs | |
Number of inputs and outputs | Number of digital outputs: 1 |
Outputs | |
Total number of outputs | 1 |
Output signal | switching signal; IO-Link; (configurable) |
Electrical design | PNP |
Number of digital outputs | 1 |
Output function | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 250 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range | |
Liquids | |
Setting range [cm/s] | 3...300 |
Greatest sensitivity [cm/s] | 3...100 |
Gases | |
Setting range [cm/s] | 200...3000 |
Greatest sensitivity [cm/s] | 200...800 |
Accuracy / deviations | |
Repeatability [cm/s] | 1...5 |
Note on repeatability | for water 5...100 cm/s; 25 °CFactory setting |
Temperature drift [cm/s x 1/K] | 0.1; (for water 5...100 cm/s; 10...70 °C) |
Temperature gradient [K/min] | 300 |
Switch point accuracy [cm/s] | ± 2...± 10; (for water 5...100 cm/s; 25 °C; Factory setting) |
Hysteresis [cm/s] | 2...5; (for water 5...100 cm/s; 25 °C; Factory setting) |
Response times | |
Liquids | |
Response time [s] | 1...2; (for a temperature gradient: 1 K/min) |
Gases | |
Response time [s] | 1...10 |
Software / programming | |
Adjustment of the switch point | pushbutton |
Interfaces | |
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
IO-Link device ID | 54 d / 00 00 36 h |
Profiles | Smart Sensor: Process Data Variable; Device Identification |
SIO mode | yes |
Required master port type | A |
Process data analogue | 2 |
Process data binary | 2 |
Min. process cycle time [ms] | 3 |
Operating conditions | |
Ambient temperature [°C] | -25...80 |
Storage temperature [°C] | -25...100 |
Protection | IP 65; IP 67 |
Tests / approvals | |
EMC | DIN EN 61000-6-2DIN EN 61000-6-3 |
Shock resistance | DIN IEC 60068-2-2750 g (11 ms) |
Vibration resistance | DIN EN 60068-2-620 g (55...2000 Hz) |
MTTF [years] | 298 |
Mechanical data | |
Weight [g] | 248.5 |
Dimensions [mm] | M18 x 1.5 |
Thread designation | M18 x 1.5 |
Materials | stainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X |
Materials (wetted parts) | stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A |
Process connection | M18 x 1,5 internal thread |
Displays / operating elements | |
Display | function10 x LED, three-colour |
Remarks | |
Pack quantity | 1 pcs. |
Electrical connection | |
Connection | Connector: 1 x M12 |